Basement bathroom plumbing explained: drain levels, sewer surcharge risk, pumped drainage, macerator conditions, ventilation, damp and approvals to check.
A basement bathroom is decided by one comparison: the level of the new fittings against the level of the drain and the chance of the sewer backing up. Establish that before choosing sanitaryware, because it determines whether water leaves by gravity, through an anti-flooding valve or by pump.
Survey the levels
Have the nearest inspection chamber located and its depth measured relative to the basement floor. A drainage survey may be needed to find routes and condition. Do not lift heavy or unsafe covers yourself.
Surcharge risk
Some sewers fill above the pipe in heavy rain. Approved Document H says that for basements containing sanitary appliances, where the sewerage undertaker considers the risk of flooding from surcharge high, basement drainage should be pumped; where the risk is low, an anti-flooding valve should be installed. Ask your sewerage company. In London that may mean Thames Water, depending on the address.
The same document says anti-flooding valves should preferably be double valve types for foul water with a manual closure, with a notice inside the building about them, and that drainage unaffected by surcharge should bypass the protection.
Pumped drainage
Where gravity is impracticable, or protection against surcharge is needed, a pumping installation is required. Package units for use inside buildings should meet BS EN 12050 and be designed to BS EN 12056-4, according to Document H.
| Question to settle | Why |
|---|---|
| Which fittings feed the pump | Sets capacity and unit type |
| Discharge height and distance | Must be within the unit's limits |
| Power failure | Pumped fittings stop working |
| Access | Servicing and blockages |
| Alarm and non-return valve | Warn and prevent backflow |
| Noise | Living space nearby |
Small bore macerators
Approved Document G allows a WC with macerator and pump to connect to small bore drainage only where there is also access to a WC discharging directly to gravity, and where the unit meets BS EN 12050-1 or 12050-3. A similar condition applies to basins, baths and showers: there must also be washing facilities draining by gravity, and the unit must meet BS EN 12050-2. LABC's note lists basements among typical uses and reminds owners to put only normal toilet waste through the unit, with regular testing and descaling.
Ventilation and damp
Below ground rooms need working extract. Approved Document F sets bathroom extract rates, with 15 litres per second for an intermittent fan. Waterproofing of walls and floors is a specialist subject; a leak and rising damp look similar, so settle the structure first.
Water supply and hot water
Supplies are usually easy to reach downwards, but check that pipes are protected, jointed where accessible and fitted with valves. Think where a leak would go: a floor with no drain keeps it.
Electrics
Bathroom electrical rules apply in basements too, and a pump needs its own suitable connection. Use a registered electrician.
Approvals
New bathrooms involving drainage, ventilation and electrics usually involve building control, and a change of use or excavation may involve planning. Flats need freeholder consent. Confirm before spending.
Living with a pumped system
Everyone using the room should know what must not be flushed, what the alarm sounds like and who services the unit. Keep the manual, the electrical isolator location and the discharge route together. Arrange access that does not involve dismantling cabinetry or breaking tiles. If the pump runs when nothing has been used, a dripping tap or a leaking cistern may be filling it, so trace that early. Record service dates, and after any flood warning check that the non-return valve and alarm still work.
Enquiring
Email floor plans, photos of the intended wall, any drain survey and the sewerage company's answer, after describing the job on the contact form.
Questions people ask
Does every basement bathroom need a pump?
No. Approved Document H calls for pumping where gravity drainage is impracticable, or where the sewerage company rates the risk of surcharge flooding as high.
Can a macerator be the only toilet?
In England it is permitted only where there is also access to a toilet discharging to a gravity system.